Foreword: Elevator equipment is one of the main building electromechanical equipment that needs to be purchased and installed in new hospitals, office buildings, commercial and residential buildings, and residences. Medical elevators are fixed lifting equipment that serve specified floors. It has a car that runs between at least two vertical or inclined steel rails with an angle of less than 15°. The car size and structure are convenient for passengers to enter and exit.
Medical Elevator Dimensions
The elevator load capacity is 450kg, 630kg, 800kg, 1000kg, 1250kg, and 1600kg. The general medical elevator has a load capacity of 1600kg.
1. Car size: 1500 (width) X2700 (length) X2300 (height); shaft size: 2400X3300X2300
2. Car size: 1800 (width) X2700 (length) X2300 (height); shaft size: 2700X3300X2300
National standard for medical elevator size
The basic car size of medical elevator size is: 1500*2400mm
<<Technical specifications for medical elevators>>
The elevator is selected according to the medical elevator model, and the basic parameters are car size 1500*2400mm, rated weight 1500KG, and speed 1M/S.
1. Standard specifications
Elevator number:
Equipment name: Gearless passenger elevator
Number of elevators: 3 in total (at least 1 of which should meet the special requirements of Article 8, see below for details)
2. Main parameters
Rated load: ≥1500KgRated speed: 1m/sLifting height: 28.8m
Dock floors: 8 floors, 8 stations, 8 doors, all facing the same directionBase station: First floor
3. Hall door device
Hall door material: First floor hairline stainless steel, other floors steel plate sprayed plasticDoor cover material Door cover specification: First floor hairline stainless steel, other floors steel plate sprayed plastic
Hall door display: Stainless steel panel, micro button (with digital display and direction indicator)
Hall door call: Standard guest caller, stainless steel panel, micro button (with digital Display and direction indicator)
4. Car installation
Car wall decoration: hairline stainless steel
Car top decoration: various styles, customers can choose
Car bottom material: PVC
Car door material: hairline stainless steel
Lighting facilities: energy-saving daylight lighting ceiling standard Car top ventilation facilities: low-noise fan ventilation Communication facilities: hidden intercom
Maintenance facilities: located below the car control box
In-car display: standard passenger elevator caller, stainless steel panel, micro button (with digital display and direction indicator)
In-car call: standard passenger elevator caller, stainless steel panel, micro button (with digital display and direction indicator)
Opening method: two doors in the middle
5. Main reference dimensions
Consider according to our company's standard civil engineering dimensions. Provide detailed civil engineering layout drawings for construction within one week after the contract is signed. The following dimensions are reference data for a single elevator. The specific data shall be subject to the data after construction. Net size of shaft: 2500mm (width) x 3000mm (depth) Top floor height: 4500mm Pit depth: 1500mm
Net size of machine room: 2500mm (width) x 5000mm (depth) x 3000mm (height) Net size of door opening: 1400mm (width) x 2200mm (height) Car outer size
Dimensions: 1500mm (width) x 2400mm (depth) Net size of door opening: 1200mm (width) x 2100mm (height)
6. Working conditions
1. Altitude shall not exceed 1000m;
2. The air temperature in the machine room shall be maintained between 5~40C;
3. The average maximum relative humidity of the wettest month at the operating location shall be 90%, and the average minimum temperature of the month shall not be higher than 25℃:
4. The fluctuation of the power supply voltage relative to the rated voltage shall be within the range of ±10%;
5. The ambient air shall not contain corrosive and flammable gases and conductive dust.
7.Power supply
1. Power supply:
Voltage: 380V+7%Frequency: 50Hz
Number of phases: 3-phase 5-wire system, neutral wire and ground wire are always separated2. Lighting power supply: Voltage: 220VFrequency: 500HzNumber of phases: single phase
8. Special requirements: At least one of the three medical elevators should meet the following three requirements
1. Accessibility (for disabled people) 2. Voice prompts (for the blind) 3. Touch buttons (for the blind)
Because different hospitals use different sizes of medical elevators due to different building scales, each hospital can choose a medical elevator based on the hospital's own building area when purchasing one. But be sure to note that the length and width ratio must be sufficient to accommodate the needs of the hospital bed and the accompanying personnel. In order to ensure the normal operation of the elevator,
and save lives in time, when purchasing an application elevator, you must choose a manufacturer with high quality to win time for life-saving and ensure the safety of the patient's life. According to this article, the requirements are sorted out with titles and directories